IBM UPS1000THV Power Supply User Manual


 
10
N
OTE: SETTINGS ARE MADE THROUGH THE SUPPLIED POWERCHUTE SOFTWARE OR
OPTIONAL SMART SLOT ACCESSORY CARDS. REFER TO THE SOFTWARE HELP GUIDES FOR DETAILS.
FUNCTION
F
ACTORY
D
EFAULT
U
SER SELECTABLE
CHOICES
D
ESCRIPTION
High Transfer Point 750TLV, 1000TLV
and 1500TLV mod-
els:127AC
750THV, 1000THV
and 1500THV mod-
els:253VAC
750TLV, 1000TLV
and 1500TLV models:
127, 130, 133, 136VAC
750THV, 1000THV
and 1500THV models:
253, 257, 261, 265VAC
If the utility voltage is usually high and the
connected equipment is specified to operate
with input voltages this high, set the high
transfer point higher to avoid unnecessary
battery usage.
Low Transfer Point 750TLV, 1000TLV
and 1500TLV mod-
els:106VAC
750THV, 1000THV
and 1500THV mod-
els:208VAC
750TLV, 1000TLV
and 1500TLV models:
97, 100, 103, 106VAC
750THV, 1000THV
and 1500THV models:
196, 200, 204, 208VAC
If the utility voltage is usually low and the
connected equipment is specified to operate
with input voltages this low, set the low
transfer point lower.