IBM IBM UPS 10000XHV Power Supply User Manual


 
14
3: USER CONFIGURABLE ITEMS
NOTE: SETTINGS ARE MADE THROUGH THE SUPPLIED POWERCHUTE BUSINESS EDITION SOFTWARE, NETWORK
MANAGEMENT CARD, OR TERMINAL MODE. REFER TO THE SOFTWARE HELP GUIDES FOR DETAILS.
FUNCTION
FACTORY
DEFAULT
USER SELECTABLE
CHOICES
DESCRIPTION
Automatic Self-Test Every 14 days
(336 hours)
Every 7 days
(168 hours),
Every 14 days
(336 hours),
On Startup Only,
No Self-Test
This function sets the interval at which
the uninterruptible power supply will
execute a self-test.
Uninterruptible
Power Supply ID
UPS_IDEN Up to eight characters Use this field to uniquely identify the
uninterruptible power supply, (i.e.
server name or location) for network
management purposes.
Date of Last Battery
Replacement
Manufacture Date mm/dd/yy Reset this date when you replace the
battery modules.
Minimum Capacity
Before Return from
Shutdown
0 percent 0, 15, 25, 35, 50, 60,
75, 90 percent
The uninterruptible power supply will
charge its batteries to the specified
percentage before it powers up con-
nected equipment, following a low-
battery shutdown.
Alarm Delay After
Line Failure
5 second delay 5 second delay,
30 second delay,
At Low Battery,
Never
The user can mute an ongoing alarm or
disable all existing alarms permanently.
Shutdown Delay 20 seconds 0, 20, 60, 120, 240,
480, 720, 960 sec-
onds
The interval is set between the times
when the uninterruptible power supply
receives a shutdown command and
actual shutdown.
Duration of Low
Battery Warning
2 minutes
(PowerChute soft-
ware provides
automatic, unat-
tended shutdown
when approxi-
mately two min-
utes of battery
runtime remain.)
2, 5, 7, 10, 12, 15, 18,
20 minutes
The low battery warning beeps become
continuous when two minutes of run-
time remain.
Change the warning interval to a higher
setting if the operating system requires
a longer interval for shutdown.
Synchronized Turn-
on Delay
0 seconds 0, 20, 60, 120, 240,
480, 720, 960 sec-
onds
The uninterruptible power supply will
wait the specified time after the return
of utility power before turn-on (to
avoid branch circuit overload).
High Bypass Point +10% of output
voltage setting
+5%, +10%, +15%,
+20%
The uninterruptible power supply will
pass this maximum voltage to con-
nected equipment during internal by-
pass operation.
Low Bypass Point -30% of output
voltage setting
-15%, -20%, -25%,
-30%
The uninterruptible power supply will
pass this minimum voltage to con-
nected equipment during internal by-
pass operation.
Output Voltage 230 Vac 200, 208, 220, 230,
240 Vac
The user is able to select the uninter-
ruptible power supply output voltage
while online. Use the voltage setting
applicable to your region.