Johnson Controls XT-9100 Network Card User Manual


 
4 Configuration Guides—XT-9100 Configuration Guide
For full details of the hardware configuration, refer to the XT-9100
Technical Bulletin (LIT-6364040).
An XT-9100 combined with expansion modules provides the following
configurations, either:
eight analog inputs/outputs, or
eight digital inputs/outputs, with digital counters associated with the
digital inputs, or
eight analog inputs/outputs and eight digital inputs/outputs, or
sixteen digital inputs/outputs, with digital counters associated with the
digital inputs within the first eight inputs/output points
The extension module address is set with the address switches on the
XT-9100. When connected to a DX-9100 controller, this address must
also be set in the DX-9100 software configuration. The address must be
unique not only on the XT-Bus, but also on the N2 Bus (Bus 91) to which
the DX-9100 is connected.
The XT-9100 must be supplied with a 24 VAC power source. All models
are suitable for 50 Hz or 60 Hz through software configuration.
For the analog inputs and outputs, the input and output type are set by
jumpers on the analog expansion module board. These settings must
comply with the software configuration settings.
Note: When an extension module is configured with 16 inputs/outputs,
the DX-9100 considers the single physical module as two logical
modules, each with eight inputs/outputs. A DX-9100 can
communicate with up to eight logical modules, with a maximum of
64 inputs/outputs.
Table 1: XT/XP/TR Model Codes
XT-9100-8004
Extension Module 24 VAC supply
XP-9102-8004
Expansion Module 6 analog inputs
2 analog outputs
XP-9103-8004
Expansion Module 8 digital outputs (triacs)
XP-9104-8004
Expansion Module 4 digital inputs
4 digital outputs (triacs)
XP-9105-8004
Expansion Module 8 digital inputs
XP-9106-8004
Expansion Module 4 digital outputs (relay)
TR-9100-8001*
Transformer, 24V/12 VA Primary: 240 VAC
TR-9100-8002*
Transformer, 24V/12 VA Primary: 220 VAC
* TR-9100 is not available in North America.