Lantronix EDS8PR Network Card User Manual


 
7: Network, Serial Line, and Tunnel Settings
EDS Device Servers User Guide 54
Under Current Configuration, Buffer Size has a Reset link that lets you reset the buffer
size value shown. If you click this link, a message tells you that you will have to reboot
the EDS. Click OK to proceed or Cancel to cancel the operation.
Figure 7-6. Tunnel – Serial Settings Page
Tunnel – Serial Settings Page
Tunnel –
Serial
Settings Page
Description
Buffer Size Enter the size of the buffer used to receive data on the serial line.
Range = 1 to 4096 bytes. Default is 2048 bytes. Changing this value
requires the EDS to be rebooted.
Read Timeout Enter the maximum number of milliseconds that the EDS waits for
incoming data on the serial line. Default is 200 milliseconds.
Wait for Read
Timeout
Select whether the EDS waits the entire Read Timeout value for incoming
data on the serial line. Waiting occurs even if there is data in the read
buffer ready to be processed. The Read Timeout is ignored only when the
read buffer completely fills with data. Choices are:
Enabled = waits the entire Read Timeout value for incoming data on the
serial line.
Disabled = does not wait the entire Read Timeout value for incoming data
(default).