Chapter 2. SPECIFICATIONS
2 - 9
(2)Voltage input range : DC 1 5V
Digital output value for input voltage is shown as follows.
Analog input voltage (V)
0.952 1 2 3 4 5 5.048
Digital output value -48 0 1000 2000 3000 4000 4047
2) G6F-AD2A
For voltage input, the corresponding input is selected by selection switch and selected input voltage range is
same through whole channels.
1) Voltage input range
: DC 1 V
Digital output value for input voltage is shown as follows.
Analog input voltage (V)
Input range selection
switch
0.952 1 2 3 4 5 5.048
-48 0 1000 2000 3000 4000 4047
Digital output value
-2048 -2000 -1000 0 1000 2000 2047
2)
Voltage input range :
DC 0 V
Digital output value for input voltage is shown as follows.
Analog input voltage (V)
Input range selection
switch
-0.12 0 2.5 5 7.5 10 10.12
-48 0 1000 2000 3000 4000 4047
Digital output value
-2048 -2000 -1000 0 1000 2000 2047
3)
Voltage input range :
DC -10 V
Digital output value for input voltage is shown as follows.
Analog input voltage (V)
Input range selection
switch
-10.24 -10 -5 0 5 10 10.24
-48 0 1000 2000 3000 4000 4047
Digital output value
-2048 -2000 -1000 0 1000 2000 2047
1 2
3
11
12
1 2
3
J1
J2
1
2
3
11
12
1
2
3
J1
J2
1
2
3
J1
J2