LG Electronics G4F-AD3A Network Card User Manual


 
Chapter 5. GM PROGRAMMING
5 -6
4) Programming
AD_INI
AD3INI
%I0.0.0
REQ
DONE
0
BASE
STAT
INI_STAT
CH
AD_CH
TYPE
DATATYPE
AVG-
EN
AVG_EN
AVG-
NUM
SLOT
ACT
3
INI_ACT
3
SLOT
CH
0
RD_STAT
STAT
CH0_DATA
DATA
0
BASE
START
S
START
AD_RD
AD3AD
REQ
DONE
AVG_NUM
%I0.0.1
INT_TO_BCD
EN
ENO
OUT
CH0_DATA
IN1
%QW0.1.0
USINT_TO_
BCD
EN
ENO
OUT
RD_STAT
IN1
%QB0.2.0
%I0.0.2
Execution condition and
Initial Setting
Base location number
specification
Available channel
enable specification
Data type specification
Average processing
enable/disable specification
Average number
value specification
Channel operation display
in the function block
initialization
Slot location
number
specification
Available channel
enable specification
Error code display in the processing
of the reading function block
Data display of A/D conversion
value of enabled channel
Slot location number
specification
A/D conversion read has
been completed normally.
This program converts the integer type of the A/D conversion value
CH0_DATA into BCD data type to display onto the BDC digital display.
Command for displaying the
error code onto BCD digital
display
Error code display in
the processing of
function block initialization
A/D conversion value
of channel 0
specification
Error code on the
reading function
This program converts the unsigned integer type of RD_STAT, which indicates the error status
of the reading function block, into BCD data type to display it onto the BDC digital display.
Command for displaying the
A/D conversion
value onto BCD
digital display
Base location
number
specification
ROW 0
ROW 1
ROW 2
ROW 3
ROW 4
ROW 5
ROW 6
ROW 7
ROW 8
ROW 9
ROW 10
ROW 11
ROW 12
ROW 13