Liebert 230V Power Supply User Manual


 
Specifications
32
12.1 Battery Cabinet Specifications
Model Number GXT2-48VBATT GXT2-72VBATT
Used w/ UPS Model
GXT2-700RT230
GXT2-1000RT230
GXT2-1500RT230
GXT2-2000RT230
GXT2-3000RT230
DIMENSIONS: mm
Unit W x D x H: mm 87 x 547 x 430 87 x 618 x 430
Shipping W x D x H: mm 268 x 692 x 585 268 x 692 x 585
WEIGHT: kg
Unit: kg 28.3 42.5
Shipping: kg 32.3 46.5
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, flame retardant, lead acid
Qty x V x Rating 2 x 4 x 12V x 7.0 or 7.2 AH 2 x 6 x 12V x 9.0 AH
Battery Mfg /
Part #
China Storage Battery /
CSBFR 1270 F2
Panasonic / UP-VW1234P1
Yuasa / REW 45-12 FR
Back-up Time See 13.0 - Battery Run Times
ENVIRONMENTAL
Operating Temp 0°C to +40°C (+32°F to +104°F)
Storage Temp -15°C to +50°C (+5°F to +122°F)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 3000 m (10,000 ft.) at 40°C (104°F) without derating
Storage Elevation 15,000 m (50,000 ft.) maximum
AGENCY
Safety
EN50091-1-1, CE compliance mark,
for both Low Voltage and EMC Directives
RFI/EMI EN 50091-2, Class B
Transportation ISTA Procedure 1A