Liebert 3000VA Surge Protector User Manual


 
Specifications
33 Liebert
®
GXT3
9.0 SPECIFICATIONS
The specifications of the Liebert GXT3 are listed in Table 11 and Table 12.
Table 11 Specifications of GXT3-700RT230 and GXT3-1000RT230 UPS
Parameters
Product model
GXT3-700RT230 GXT3-1000RT230
Model Rating 700VA/630W 1000VA/900W
Dimensions, D x W x H, mm (in)
Unit 497 x 430 x 85 (19.6 x 16.9 x 3.3)
Shipping 617 x 570 x 262 (24.3 x 22.4 x 10.3)
Weight, kg (lb)
Unit 16.8 (37)
Shipping 20 (44)
Input AC
Voltage Range (typical) 230VAC nominal; variable based on output load
90% ~ 100% loading 177VAC/280VAC
70% ~ 90% loading 168VAC/280VAC
30% ~ 70% loading 150VAC/280VAC
0 ~ 30% loading 115VAC/280VAC
Frequency 40Hz ~ 70Hz; Auto Sensing
Input Power Receptacle C14
Output AC
AC-AC Efficiency > 88% AC-AC, minimum
Output Receptacles C13 × 6
Voltage 220/230/240VAC (user configurable); ±3%
Frequency 50Hz or 60Hz
Waveform Sine wave
Mains (AC) Mode Overload 200% for 2 seconds; 150% for 1 minute with transfer to bypass
Internal Battery Charger
Charger Current 1.3
Battery
Type Valve-regulated, nonspillable, lead acid
Qty × V× Rating 4 × 12V × 5.0Ah
Battery Mfr/Part# YUASA/NPH5-12; CSB/ HR 1221W; CSB/GP1245
Backup Time See Table 15 - Battery run times
Recharge Time
3 hours to 90% capacity after full discharge with 100% load till UPS
auto-shutdown (Internal Batteries Only)
Environmental Requirements
Operating Temp 0ºC to +40ºC (+32ºF to +104ºF); Table 14 - Operating temperature parameters
Storage Temp -15ºC to +50ºC (5ºF to 122ºF)
Relative Humidity 0%RH to 95%RH, non-condensing
Operating Elevation Up to 3000m (10,000 ft.) at 25ºC (77ºF) without derating
Storage Elevation 15,240 (50,000 ft.) maximum
Audible Noise
< 46 dBA, at 1 meter (3.2ft) from the rear
< 43 dBA, at 1 meter (3.2ft) from the front or sides
Agency
Safety IEC/EN/AS 62040-1:2008, GS mark
RFI/EMI IEC/EN/AS 62040-2 2nd Ed (Category C2) = CISPR22 Class A
Surge Immunity IEC/EN 62040-2 2nd Ed (IEC/EN 61000-4-5)
Transportation ISTA Procedure 1A