liebert.upstech@emerson.com
Internal Battery
+ 4 External Battery
Cabinets
10% 480 480 480 346 480
20% 480 340 315 301 303
30% 338 316 215 186 187
40% 322 220 184 156 156
50% 305 198 157 141 141
60% 217 166 145 126 127
70% 202 158 133 107 108
80% 186 149 120 95 97
90% 164 141 105 79 81
100% 159 133 96 72 73
The times above are approximate. They are based on new, fully charged batteries with 100% resistive loads
and an ambient temperature of 77°F (25°C). To increase this time, turn Off non-essential loads (such as idle
computers and monitors) or add optional external battery cabinets.
Table 15 Battery run times (continued)
Number of
Batteries/Cabinets
Load Percent
of Capacity
Run Time, Minutes
700VA 1000VA 1500VA 2000VA 3000VA