Liebert 4000 Power Supply User Manual


 
Specifications 13
Electrical specifications of the fuse panels
The electrical specifications of the fuse panels are described in
Table 15.
3.3.2 Circuit Breaker Panels
Mechanical specifications of the circuit breaker panels
The mechanical specifications of the circuit breaker panels are described in
Table 16.
Table 15 Electrical specifications of the fuse panels
Panel number Figure
Fuses
Busbar
capacity
Quantity Capacity
(20) QFF 0-5 A
60 A max
Figure 5
20 0-5 A 60 A
(16) QFF 0-5 A &
(12) ABS 5-30 A
300 A max
Figure 6
16
12
0-5 A
0-30 A
300 A
(16) QFF 0-5 A &
(6) TPN 5-30 A
250 A max
Figure 7
8 0-30 A 250 A
(8) TPN 5-30 A
250 A max
Figure 8
8 31-60 A 300 A
(4) RS100P 70-100 A
300 A max
Figure 9
4 70-100 A 300 A
(4) CRS200P 150-200 A
600 A max
(4) CRS200P 150-200 A (w/load shunts)
600 A max
Figure 10
4 101-200 A 600 A
(4) TPL 225-600 A
1600 A max
Figure 11
4 225-600 A 1600 A
(18) TPS 1-70 A
600 A max
Figure 12
18 0-70 A 600 A
Table 16 Mechanical specifications of the circuit breaker panels
Panel description Figure Height Width Weight
(24) Plug-In 1-100 A
900 A max
Figure 13
165 mm
(6.5 in.)
584 mm
(23.0 in.)
9.1kg
(20 lb.)
(4) 70-250 A
900 A max *
Figure 14
178 mm
(7.0 in.)
584 mm
(23.0 in.)
10.5 kg
(25 lb)
(2) 400 A
Figure 15
178 mm
(7.0 in.)
584 mm
(23.0 in.)
10.5 kg
(25 lb)
(1) 600-700 A
Figure 16
178 mm
(7.0 in.)
584 mm
(23.0 in.)
10.5 kg
(25 lb)
* The 250 A circuit breaker has two poles, thus the panel can accommodate a maximum of two 250 A breakers.