BATTERY REPLACEMENT PROCEDURES
CAUTION A battery can present a risk of electrical shock and high short
circuit current. The following precautions should be observed before replacing
the batteries:
- Turn off and disconnect the UPS from the utility power prior to opening
the battery replacement door.
- Remove rings, watches, and other metal objects.
- Use a Phillips (cross head) screwdriver with insulated grips.
- Do not lay tools or other metal objects on top of the batteries.
- If the battery replacement kit is damaged in any way or shows signs of
leakage, contact your dealer immediately.
- Do not dispose of batteries in a fire, the batteries may explode.
- If you feel unqualified to replace the batteries, do not open the battery
door. Call Liebert Technical Support (LTS). World Wide Technical
Support numbers are located at the end of this section.
MINI-TOWER BATTERY REPLACEMENT
B
a
t
t
e
r
y
c
o
n
n
e
c
t
o
r
B
a
t
t
e
r
y
d
o
o
r
s
c
r
e
w
s
FOR 700/1000 VA MINI-TOWER MODELS:
1. Gently lay the UPS on its right side.
2. Loosen and remove the five screws on the battery door. Remove the door
by sliding it toward the rear of UPS and lifting it off. Lay the battery door
aside for reassembly.
3. Gently pull battery wiring out and disconnect the battery connector.
4. Grasp the battery assembly, and pull it out of the UPS.
5. Unpack the new battery assembly taking care not to destroy the packing.
Compare new and old battery assemblies to make sure they are the same
quantity and voltage rating (see specifications). If so, proceed with step 6;
otherwise STOP and contact your dealer or LTS.
6. Slide the new battery assembly into the cavity, noting the connector is facing
outward. Connect the battery connector together.
NOTE: There will be a small spark when connecting the battery connector.
This is normal and will not harm you or the UPS.