Liebert 700-3000 VA Power Supply User Manual


 
8
12. Plug the UPS into a dedicated wall receptacle properly protected by a circuit
breaker or fuse in accordance with the National And Local Codes. Use a 15
amp rated device for the 1000, or 1500 VA units, a 20 amp device for the
2000 VA unit, and a 30 amp device for the 3000 VA unit. The wall
receptacle must be grounded.
13. Locate UPS indoors in a controlled environment, where it cannot be
accidentally turned off. Locate it in an area of unrestricted airflow around the
unit, away from water, flammable liquids, gases, corrosives, or conductive
contaminants. Maintain a minimum of 4 inches (100 mm) clearance in front
and rear of the UPS. Maintain an ambient temperature range of 32° to 104°
F (0° to 40° C).
NOTE: UPS operation in temperatures above 77° F (25° C) reduces battery
life.
14. Turn on the UPS by pressing the On button; then turn on the connected load
equipment. The UPS is ready for normal operation.
OPTIONAL BATTERY CABINET(S) INSTALLATION
Up to two optional battery cabinets may be connected to the UPS to provide
additional run time. Battery cabinets are designed to be placed on either side or
beneath the UPS.
1. Unpack the UPS battery cabinet(s) carefully noting the packing method.
Retain the box and packing material for possible future shipment.
2. CAUTION: The battery cabinet(s) are heavy (see specifications). Take
proper precautions when lifting or moving them.
3. Visually inspect the UPS for freight damage. Report damage to the carrier
and your dealer.
4. Follow the same installation instructions used earlier for the UPS (tower or
rack-mount).
5. Attach external battery cabinets as shown, using the enclosed metal
securing plate to prevent tip-over.
6. Connect the supplied cable to the battery cabinet then to the UPS.
7. Turn on the breaker on the rear of the battery cabinet.
Battery Cabinet Installation Diagram
SECURING PLATE
BREAKER
DISCONTINUED
PRODUCT