Liebert 700-3000 VA Power Supply User Manual


 
21
UPSTATION GXT BATTERY RUN TIMES
(Discharge times are at 25° C ambient)
Internal Battery (minutes)
Load% 700MT 1000MT 1000RT 1000RTE 1500RT 2000RT 3000RT
10% 52 94 94 169 78 160 101
20% 40 45 45 127 39 83 51
30% 32 33 33 94 27 47 28
40% 24 24 24 68 20 34 20
50% 18 18 18 49 15 27 15
60% 15 14 14 36 11 21 12
70% 12 12 12 28 9 18 10
80% 10 9 9 23 7 15 8
90% 8 7 7 19 6 13 7
100% 6 6 6 17 5 11 6
Internal Battery + 1 External Battery Cabinet (minutes)
Load% 700MT 1000MT 1000RT 1000RTE 1500RT 2000RT 3000RT
10% N/A N/A 479 552 408 343 273
20% N/A N/A 255 335 215 204 140
30% N/A N/A 150 210 126 133 78
40% N/A N/A 110 152 95 100 57
50% N/A N/A 85 115 75 77 44
60% N/A N/A 66 88 57 60 35
70% N/A N/A 56 72 48 50 30
80% N/A N/A 48 62 40 43 26
90% N/A N/A 41 52 35 36 22
100% N/A N/A 35 45 29 31 18
Internal Battery + 2 External Battery Cabinets (minutes)
Load% 700MT 1000MT 1000RT 1000RTE 500RT 2000RT 3000RT
10% N/A N/A 848 920 718 623 444
20% N/A N/A 425 505 365 345 236
30% N/A N/A 243 303 208 211 138
40% N/A N/A 196 238 164 156 100
50% N/A N/A 168 198 139 120 75
60% N/A N/A 133 155 112 94 59
70% N/A N/A 109 125 94 81 50
80% N/A N/A 89 103 78 70 43
90% N/A N/A 77 88 68 62 36
100% N/A N/A 66 76 58 54 31