Liebert 700-3000 VA Power Supply User Manual


 
25
SPECIFICATIONS
MODEL NUMBER GXT700MT-230 GXT1000MT-230
MODEL RATING VA/W 700 / 490 1000 / 700
DIMENSIONS: mm (in)
Unit
W x D x H
162 x 430 x 225
(6.4 x 15.6 x 8.9)
162 x 430 x 225
(6.4 x 15.6 x 8.9)
Shipping
W x D x H
280 x 502 x 362
(11.0 x 19.75 x 14.25)
280 x 502 x 362
(11.0 x 19.75 x 14.25)
WEIGHT: kg (lbs)
Unit 13.1 (28.8) 15.8 (34.8)
Shipping 15.0 (33.0) 17.7 (39.0)
INPUT AC PARAMETERS
Voltage Range (typical) 230 VAC nominal; variable based upon output load
100% - 70% Loading 160-163 VAC to 273-276 VAC
70% - 30% Loading 140-143 VAC to 273-276 VAC
30% - 0% Loading 120-122 VAC to 273-276 VAC
Frequency 48.1 - 51.9 Hz or 57.6 - 62.4 Hz; auto sensing
Input connector IEC320-10A IEC320-10A
OUTPUT AC PARAMETERS
Output Sockets (4) IEC320-10A (4) IEC320-10A
Voltage 208/220/230/240 (switch selectable) VAC; ±3%
Frequency 50 Hz or 60Hz
Waveform Sinewave
Main Mode Overload 200% for 8 cycles; 130% for 10 seconds with transfer to bypass
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, lead acid
Qty. x Voltage x Rating 2 x 12V x7 or 7.2 AH 3 x 12V x 7 or 7.2 AH
Back-up Time See Typical Battery Discharge Curves
ENVIROMENTAL
Operating Temperature 0° C to +40° C (+32° F to +104° F)
Storage Temperature -15° C to +50° C (+5° F to +122 °F)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 3000 m (10,000 ft.) at 40° C without derating
Storage Elevation 15.000 m (50,000 ft.) maximum
Audible Noise <45 dBA, at 1 meter
AGENCY
Safety EN50091-1, TUV/GS Listed, CE Low Voltage Directive compliant
RFI/EMI EN55022, Class B; CE EMC Directive compliant
Immunity
IEC 801-2, Level 4 / IEC 801-3, Level 3 / IEC 801-4,
Level 4 / IEC801-5,Level 3