Liebert GXT2-10000RT208 Power Supply User Manual


 
Installation and Configuration
16
6.3.3 Add an Output Power Distribution Module—Optional
To add an optional output distribution module to the Liebert GXT2 10000RT208:
1. Remove the four screws securing the blank output distribution cover plate to the rear of the UPS.
The cover is at top left corner in the tower configuration and at the bottom left in the rack
configuration.
2. Set the screws aside to attach output distribution module to UPS.
3. Snap together the electrical connectors on the UPS and on the output distribution.
4. Use the screws removed in Step 2 to attach the output distribution to the rear of the UPS.
OUTPUT L1
OUTPUT BREAKER 30A 250V~n
OUTPUT L2
T20A 125V-
PUSH TO
RESTART
T20A 125V-
PUSH TO
RESTART
T20A 125V-
PUSH TO
RESTART
T20A 125V-
PUSH TO
RESTART
T20A 125V-
PUSH TO
RESTART
Electrical Connector
snaps to connector
inside UPS
Screw holes
to attach to UPS
Screw holes
to attach to UPS
Output Distribution
Cover Plate
Hardwire
Terminal
Block
Cover
REAR VIEW
Liebert GXT2 10000RT208
Optional Output
Power Distribution
Module
(PD-101 shown)
DISCONTINUED