Liebert GXT2-10000RT208 Power Supply User Manual


 
Troubleshooting
42
Using the configuration program, the user may specify the number of GXT2-288VBATT external bat-
tery cabinets attached to the UPS. The factory default is programmed for internal batteries only.
Table 6 shows estimated run times at different loads.
Table 6 Battery run times
Battery/External
Cabinets Load%
10000VA Run Time
in Minutes
Battery/External
Cabinets Load%
10000VA Run Time
in Minutes
Internal Battery
10% 107
Internal Battery
+ 1 LRT Battery
Pack
10% 548
20% 52 20% 284
30% 31 30% 217
40% 22 40% 151
50% 16 50% 107
60% 13 60% 86
70% 10 70% 66
80% 9 80% 55
90% 7 90% 47
100% 6 100% 40
Internal Battery
+ 1 External Battery
Cabinet
10% 251
Internal Battery
+ 2 LRT Battery
Pack
10% 1030
20% 118 20% 538
30% 74 30% 332
40% 52 40% 269
50% 39 50% 231
60% 32 60% 195
70% 26 70% 158
80% 22 80% 125
90% 19 90% 109
100% 17 100% 96
Internal Battery
+ 2 External Battery
Cabinets
10% 333
Internal Battery
+ 3 LRT Battery
Pack
10% 1473
20% 216 20% 821
30% 118 30% 520
40% 85 40% 382
50% 66 50% 289
60% 53 60% 264
70% 44 70% 238
80% 38 80% 215
90% 32 90% 189
100% 28 100% 165
Internal Battery
+ 3 External Battery
Cabinets
10% 494
Internal Battery
+ 4 LRT
10% 1973
20% 265 20% 1053
30% 191 30% 672
40% 119 40% 515
50% 92 50% 406
60% 75 60% 304
70% 62 70% 280
80% 54 80% 263
90% 47 90% 243
100% 41 100% 224
Internal Battery
+ 4 External Battery
Cabinets
10% 590
20% 295
30% 236
40% 178
50% 119
60% 98
70% 82
80% 71
90% 61
100% 54