Liebert GXTTM Power Supply User Manual


 
19
Connecting the UPS Power cables
Power cables connect to screw terminals on a terminal block that is located
behind the rear mounted cable box (see figure). The cables enter the UPS
through a Gland Plate attached to the rear of the UPS. The Gland Plate must first
be removed and drilled to suit the glands or bushes for the cables used. Ensure
that the glands are sized so that they hold the cables securely.
GXT 6 / 10 kVA Connection Diagram
Connection of optional remote battery cabinets.
Full installation instructions are provided with these cabinets. Safety/EMC
certification limits the use of these terminals to Liebert supplied options.
Output connections GXT 6000/10000-X models only
Models whose part number ends with an “X” are fitted with an isolating output
transformer. The output of this transformer is referenced to earth at the neutral
terminal, remove this earth-neutral link when required by local electrical codes.
6kVA
10kVA
UPS Power Section
To Mains To Load
To External Battery
(Optional)