24
Battery Run Times
Load %
6kVA
6kVA + (1)
GXT240VBATT
6kVA + (2)
GXT240VBATT
10% 69 250 360
20% 58 197 301
25% 52 174 278
30% 48 155 248
40% 33 117 190
50% 23 88 140
60% 17 73 110
70% 14 60 94
75% 12 54 85
80% 11 50 77
90% 9 42 68
100% 8 37 59
Load %
10kVA
10kVA + (1)
GXT240VLRT
10kVA + (2)
GXT240VLRT
10% 71 480 900
20% 60 390 730
25% 55 345 655
30% 49 305 585
40% 39 230 450
50% 29 164 335
60% 23 129 265
70% 20 105 225
75% 18 93 205
80% 17 85 190
90% 14 70 155
100% 12 60 125
Note: All run times are in minutes, assume fully charged batteries, and
are typical at 25
O
O
C (77
O
O
F) with resistive loads.