Liebert GXTTM Power Supply User Manual


 
25
SPECIFICATIONS
MODEL NUMBER
GXT6000T-230 GXT10000T-230
MODEL RATING VA/W (max)
6000 / 4200 10000 / 7000
DIMENSIONS: mm (in)
Unit
W x D x H
260 x 555 x 803
(10.5 x 22.0 x 31.5)
340 x 650 x 960
(13.5 x 25.5 x 38.0)
Shipping
W x D x H
400 x 850 x 1065
(16.0 x 33.5 x 42.0)
510 x 840 x 1235
(20.0 x 33.0 x 48.5)
WEIGHT: kg (lbs)
Unit 99 (218) 187 (412)
Shipping 130 (288) 227 (500)
Input/Output Connections
Hardwire terminal block
INPUT AC PARAMETERS
Voltage Range (typical) 230 VAC nominal; variable based upon output load
100% - 90% Loading 186 VAC to 280 VAC; ±5.0 VAC
90% - 70% Loading 159 VAC to 280 VAC; ±5.0 VAC
70% - 30% Loading 139 VAC to 280 VAC; ±5.0 VAC
30% - 0% Loading 119 VAC to 280 VAC; ±5.0 VAC
Frequency 46.6 52.4 Hz or 57.1 - 62.9 Hz; auto sensing
OUTPUT AC PARAMETERS
Voltage 208/220/230/240 VAC (switch selectable); ±3%
Frequency 50 Hz or 60 Hz; auto sensing
Waveform Sinewave
Main Mode Overload 200% for 8 cycles; 130% for 10 seconds with transfer to
bypass
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, lead acid
Qty. x Voltage x Rating 20 x 12V x 7.0 Ah 40 x 12V x 7.0 Ah
Back-up Time 7 min. minimum 10 min. minimum
Recharge Time
(Internal Batteries Only)
7 hours to 95% capacity after full discharge into 100%
load
ENVIROMENTAL
Operating Temperature 0° C to +40° C (+32° F to +104° F)
Storage Temperature -15° C to +50° C (+5° F to +122 °F)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 3000 m (10,000 ft.) at 40° C without derating
Storage Elevation 15.000 m (50,000 ft.) maximum
Audible Noise <55 dB ”A” at 1 metre <65 dB ”A” at 1 metre
AGENCY
Safety EN50091-1-1; TUV/GS Listed; CE Low Voltage Directive
EMI/EMC EN50091-2, Class A; CE EMC Directive
Immunity IEC 801-2, Level 4 / IEC 801-3,
Level 3 / IEC 801-4, Level 4 / IEC801-5,Level 3