Liebert Power Supply Power Supply User Manual


 
POWERSURE™ INTERACTIVE TYPICAL
BATTERY DISCHARGE CURVES
(Discharge times are at 25° C ambient)
0 25 50 75 100
0
20
40
60
80
Percent Load
Run Time (Mins)
0 25 50 75
100
0
20
40
60
80
Percent Load
Run Time (Mins)
0 25 50 75 100
0
20
40
60
80
Percent Load
Run Time (Mins)
0 25 50 75
100
0
20
40
60
80
Percent Load
Run Time (Mins)
700 VA 1000 VA
1400 VA 2200 VA
AUDIBLE ALARM CONDITIONS
CONDITION ALARM
Battery mode (mains
failure)
One short beep every ten seconds; more
than two minutes of run time remaining
Low battery Two short beeps every five seconds; less than
two minutes of run time remaining
Battery replacement Two second beep every minute
UPS output overload One short beep every second
UPS fault Continuous tone
FUSE REPLACEMENT PROCEDURES FOR 700 VA
MODELS
CAUTION: Before changing the supply fuse, turn off the UPS, and unplug the input
cord from the AC input power supply and from the UPS.
1. Remove the fuse holder by inserting a flat blade screw driver into the slot and
pulling out as indicated in the figure above.
2. Remove the input fuse.
3. Remove the spare fuse from its position by using the screw driver to push it out.
4. Place spare fuse in the input fuse position, and replace the fuse holder. The fuse
holder will lock into position.
5. Reconnect the input power lead to the UPS, and the input power lead to the input
AC supply.
6. Restart the UPS. The UPS is ready for normal operation.
NOTE: For 1000, 1400, and 2200 VA units press the reset circuit protector button.
Insert flat blade screw
driver into slot and pull
fuse holder out to remove
AC Inlet
Fuse Holder
Input Fuse
Spare Fuse