Liebert Power Supply Power Supply User Manual


 
CAUTION: The UPS and connected load total earth leakage current
must not exceed 3.5 milliamperes. If the connected load earth leakage
current is likely to exceed 2.5 milliamperes or you are unsure, then
convert the input lead attachment to either a fixed wiring installation or an
industrial plug/socket (e.g. CEE 17 connector). This task should be
carried out by a competent electrical engineer who is conversant with
local electrical codes/regulations.
9. The UPS output supply sockets may be electrically live whenever the
input power lead is plugged into the mains supply socket. Turning the
UPS OFF does not electrically isolate the internal parts. To isolate the
UPS, turn the UPS OFF then isolate it from the mains supply.
10. When installing the UPS or making input and output connections, comply
with relevant safety standards (e.g. IEC950, VDE0805, EN50091-1).
11. This equipment complies with the requirements of the EMC Directive
89/336/EEC and the published technical standards. Continued
compliance requires installation in accordance with these instructions
and the use of manufacturer approved accessories with output cables
not exceeding 10 metres (30 ft.) in length. Use a shielded cable for the
external communications interface.
12. Operate UPS only from a properly earthed, 50 Hz or 60 Hz, 220-240
VAC mains supply. Models are available for 100-127 VAC supply
voltages.
13. Route power supply leads so they are not walked on or pinched.
14. Never block or insert any object into the ventilation holes or other
openings. Maintain a minimum clearance of 100 mm (4 inches) all
around the UPS for proper air flow and cooling.
15. Operate the UPS in an indoor environment only, with an ambient
temperature range of 0° C to +40° C (32° F to +104° F). Install it in a
clean environment, free from moisture, flammable liquids, gasses, or
corrosive substances.
16. Storing magnetic media on top of the UPS may result in data loss or
corruption.
17. Turn the UPS off and unplug the UPS before cleaning. Use only a soft
cloth, never liquid or aerosol cleaners.
18. This equipment can be operated by individuals without previous training.
INTRODUCTION & SYSTEM DESCRIPTION
Congratulations on your choice of the Liebert PowerSure™ Interactive Uninterruptible
Power System (UPS). It provides conditioned power to microcomputers and other
sensitive electronic equipment.
Upon generation, AC power is clean and stable. However, during transmission it may
be subject to voltage sags, spikes, or complete power failure which may interrupt
computer operations, cause data loss, or even damage equipment. The
PowerSure™ Interactive protects equipment from these disturbances.
The PowerSure™ Interactive comes in nominal power ratings of 700, 1000, 1400, or
2200 VA. Complete specifications appear near the end of this section.
The PowerSure™ Interactive is a compact, “line interactive” UPS. A “line interactive”
UPS continuously conditions and regulates its output voltage, whether the mains
power is present or not. It supplies connected equipment with clean sinewave power,
to simulate as much as possible, the power generated by the mains. Sensitive
electronic equipment operates best from sinewave power.
For ease of use, the PowerSure™ Interactive contains a light emitting diode (LED)
bar display to indicate either “load percentage” or “battery capacity” depending upon
the mode of operation. It also provides self diagnostics, a combination alarm
silence/battery test button, and two levels of alarms when the unit is operating on
battery.
The PowerSure™ Interactive has an interface port for communications between the
UPS and a LAN server or other computer system. This port provides detailed
operating information including voltages, currents, and alarm status to the host
system when used in conjunction with Liebert SiteNet® software. SiteNet® software
can also remotely control UPS operation.
GLOSSARY OF SYMBOLS
Indicates AC Input
Indicates AC Output
Indicates Caution: Note the accompanying instruction
Indicates the position of a fuse
Requests the user to consult the manual for additional information
Indicates that the unit contains a valve regulated lead acid battery
4 3