Liebert PS250-50S, PS400-50S, PS600-50S Power Supply User Manual


 
10
SPECIFICATIONS
Model # / Stock #
PS250-50/PS250-50S PS400-50 / PS400-50S PS600-50 / PS600-50S
Model Rating
250 VA / 150 W 400 VA / 240 W 600 VA / 360 W
Dimensions: mm
Unit (W x D x H) 90 x 262 x 175 109 x 262 x 186 124 x 262 x 216
Shipping (W x D x H) 181 x 365 x 303 212 x 482 x 292 237 x 482 x 334
Weight: Kg
Unit 4 5.7 9
Shipping 4.6 7 10.5
AC Parameters
Receptacles (2) CEE-22 (4) CEE-22 (4) CEE-22
Input Voltage Range 180-300 VAC, Single Phase, 2 Wire Plus Earth
Low Voltage Transfer Point 190 VAC, User Selectable to 180 or 200 VAC
High Voltage Transfer Point 270 VAC 270 VAC, User Selectable to 280 VAC
Input Frequency Range 47 – 53 Hz, 57 63 Hz
Spike Protection 80 Joules
Output Voltage (on battery) 230 VAC, ± 5%
Output waveform (on battery) Stepped Sine Wave
Max. Output Current at 230 V 1.1 A 1.7A 2.6A
Output Frequency 50 or 60 Hz, ± 5%
Max. Overload Capacity 115% of Power Rating
Battery
Type Valve-Regulated Lead Acid
Qty x Voltage x Rating 1 x 12 V x 4.5 AH 1 x 12 V x 7 AH 2 x 12 V x 7 AH
Back-up Time 6 minutes at full load
Time from Low Battery Alarm
to Shutdown
Approximately 2 Minutes, depending on load
Recharge Time 8 – 10 Hours to 90% Capacity
Battery Life 3 – 5 Years Typical
Transfer Time to/from Inverter 2 – 6 msec. Typical
Agency Approvals
Safety EN 50091-1
RFI Meets EN 55022 Class B, IEC 801-2, 3, 4
Surge Protection Meets IEC 801-5 (Draft)
MTBF (Bellcore Method) 100,000 Hours (Excluding Battery)
Environmental Standards
Operating Temperatures +10° C to +40° C
Storage Temperatures -20° C to +40° C (High Temperatures Reduce Battery Life)
Cooling Convection
Audible Noise Less than 40 dB @ 1 meter
Operating Elevation Up to 3,000 m
Storage Elevation Up to 10,000 m