Liebert PSP Power Supply User Manual


 
13
Transfer Voltage Selectors (DIP Switches)
The two-position DIP switch control on the rear panel, as shown
below, allows the operator to select the utility transfer voltage at
which the UPS will switch to battery power.
The factory default settings are 185VAC - 270VAC. DIP switch posi-
tions for each voltage setting are as follows:
DIP switch settings
Left Right Setting
Up Up 185 - 270VAC (default)
Up Down 185 - 280VAC
Down Up 175 - 270VAC
Down Down 175 - 280VAC
!
CAUTION
Never change the voltage settings while the UPS is ON and
powering connected loads. Change DIP switches only when
the UPS is OFF.
!
CAUTION
To ensure protection of the connected equipment, the DIP
switch settings should match the nominal utility input
voltage. DIP switch settings not matching the nominal
utility could potentially damage connected equipment.
185-270V
185-280V
175-270V
175-280V
Refer to user's manual
for voltage setting
Rear of UPS
DIP Switches