12
MAINTENANCE
The UPStation® GX UPS normally requires very little maintenance.
Keep the sealed, maintenance-free batteries fully charged to obtain designed life of 5
years. During normal operation, the UPS continuously charges the batteries.
To store or deactivate the UPS for any length of time, charge it no less frequently than once
every 6 months. Switch UPS OFF when not connected to the utility AC. To charge the
batteries, connect the UPS to the utility and turn it ON for a minimum of 4 hours.
Replace batteries after 5 years or sooner if exposed to adverse conditions. Refer battery
replacement to qualified service personnel only. Heed cautions at the front of this manual
at all times. Call Liebert Technical Support at 1-800-222-5877 for battery replacement
instructions.
Battery Safety Precautions
WARNING: Battery maintenance procedures expose hazardous live parts. Refer
servicing to qualified personnel only.
CAUTION: Call a qualified battery supplier to dispose of batteries according to local
environmental laws. Do not open or mutilate batteries. Released electrolyte is harmful to
skin and eyes and may be toxic.
BATTERY RUN TIMES
20 30 40 50 60 70 80 90 100
100
50
150
200
250
300
350
400
3000 VA RUN TIME (Mins)
PERCENT LOAD
One
External
Cabinet
Two
External
Cabinets
Three
External
Cabinets
20 2030 3040 4050 5060 6070 7080 8090 90100 100
100 100
200 200
300 300
400 400
500
500
600
600
1000 VA RUN TIME (Mins) 1500-2100 VA RUN TIME (Mins)
PERCENT LOAD PERCENT LOAD
Internal
Internal
+1
Cabinet
Internal
+2
Cabinets
0
0