MGE UPS Systems 12 kVA Power Supply User Manual


 
51033212EN/AC - Page 27
1. Secure the connection module using the two screws .
2. Reconnect the connection cable(s) to the battery module(s).
3. Switch the battery circuit breaker(s) to the ON position
and check that LED is ON.
Check that UPS personalization settings still
correspond to the equipment to be supplied
(see section 3.5).
4. Press button and wait 20 seconds.
5. Check that LED is ON.
If LED is not ON, do not switch the manual
bypass to the intermediate position and call the
after-sales support department.
6. Turn the manual bypass switch from the BYPASS position
to the intermediate position and check that LED is OFF.
7. Turn the manual bypass switch from the intermediate
position to the NORMAL position.
LED goes OFF and LED
goes ON.
The connected equipment is again protected by the UPS.