MGE UPS Systems 12 kVA Power Supply User Manual


 
51033212EN/AC - Page 9
1. Presentation
1.3 Options
Transformer for galvanic isolation or earthing arrangement change
Important: to simplify installation, connect the Comet EXtreme Transformer downsteam of the UPSs.
Visit our Web site: www.mgeups.com/products/pdt230/smallups/extreme/transfo.htm
Nominal power
Nominal current
Input voltage
Voltage drop
Frequency
Isolation (EN 61558-1-2-4)
Operating temperature
Max. operating rel. humidity
Derating / altitude
Natural ventilation
Dimensions HxWxD (tower)
Dimensions HxWxD (rack 4U)
Weight (tower)
Weight (rack)
Comet EXtreme
Transfo 4.5 - 6 kVA
Comet EXtreme
Transfo 9 - 12 kVA
6 kVA
32 A
230V (+15%, -20%)
2.2%
50/60 Hz (+/-10%)
3.75 kV / 5 M ohms
From 0° to +40°C
95%
Pn-10% > 1000 m
IP20 ANAN
443 x 173 x 465 mm
177 x 483 x 462 mm
44 kg
48 kg
12 kVA
63 A
230V (+15%, -20%)
1.7%
50/60 Hz (+/-10%)
3.75 kV / 5 M ohms
From 0° to +40°C
95%
Pn-10% > 1000 m
IP20 ANAN
443 x 216 x 465 mm
177 x 483 x 462 mm
62 kg
67 kg
EPO (Emergency Power Off)
Available for both tower and rack versions of UPSs with standard backup times and for the battery
extensions, the EPO (Emergency Power Off) option lets you simultaneously switch off the UPS battery circuit
breaker and the upstream circuit breaker of your installation by connecting both of them to a single
emergency off button (not supplied).
For more details, visit our Web site: www.mgeups.com/products/pdt230/smallups/extreme/epo.htm
Battery extensions for UPS backup times of 80 minutes
Comet EXtreme offers a standard
backup time of 9/12 minutes.
To increase backup time, it is possible
to connect Comet EXtreme EXB
modules to the UPSs.
Visit our Web site: www.mgeups.com/
products/pdt230/smallups/extreme/
guide.htm.
Battery extensions for 4.5 or 6 kVA Comet EXtreme:
+++
Comet EXtreme
4.5 / 6 kVA
Comet
EXtreme
EXB
4.5 /
6 kVA
4.5 kVA:
6 kVA:
12 min
9 min
30 min
23 min
54 min
40 min
80 min
75 min
Comet
EXtreme
EXB
4.5 /
6 kVA
Comet
EXtreme
EXB
4.5 /
6 kVA
Comet
EXtreme
EXB
4.5 /
6 kVA