MGE UPS Systems 1500C Power Supply User Manual


 
51031998EN/AA - Page 27
6. Appendices
6.1 Technical characteristics
Operating conditions
Relative humidity: 20 to 90 % without condensation.
Temperature: 0 to 40° C.
Simplified diagram
Input voltage and frequency
160 V to 276 V +/- 5 % (at rated power)
50 Hz or 60 Hz +/- 5 %
Output voltage and frequency
200* / 210 / 220 / 230 / 240 V
50 Hz or 60 Hz +/- 5 %
* Except TUV