1. Presentation
1.4 Options
Transformer for galvanic isolation or earthing arrangement change
Important: to simplify installation, connect the Pulsar EXtreme Transformer downsteam of the UPSs.
Visit our Web site: www.mgeups.com/products/pdt230/smallups/extreme/transfo.htm
Nominal power
Nominal current
Input voltage
Voltage drop
Frequency
Isolation (EN 61558-1-2-4)
Operating temperature
Max. operating rel. humidity
Derating / altitude
Natural ventilation
Dimensions HxWxD (tower)
Dimensions HxWxD (rack 4U)
Weight (tower)
Weight (rack)
Pulsar EXtreme Transformer
3 kVA
16 A
230V (+15%, -20%)
< 3%
50/60 Hz (+/-10%)
3.75 kV / 5 M ohms
From 0° to +40°C
95%
Pn-10% > 1000 m
IP20 ANAN
443 x 173 x 465 mm
177 x 483 x 462 mm
24 kg
28 kg
Battery extensions for UPS backup times of 66 minutes
Pulsar EXtreme offers a standard
backup time of 9 minutes.
To increase backup time, it is possible
to connect Pulsar EXtreme EXB
modules to the UPSs.
Visit our Web site: www.mgeups.com/
products/pdt230/smallups/extreme/
guide.htm.
Battery extensions for Pulsar EXtreme:
The Pulsar EXtreme EXB modules are available in "tower" and in "rack" models.
The Pulsar EXtreme EXB modules come with their connection cables.
+++
Pulsar
EXtreme
EXB
Pulsar
EXtreme
EXB
Pulsar
EXtreme
EXB
Pulsar
EXtreme
EXB
9 min 20 min 36 min 66 min
Pulsar EXtreme