MGE UPS Systems 3200RT Power Supply User Manual


 
3400753300/AE - Page 21
Indication Signification Correction
The outlets are not supplied One of the protection circuit breakers 6 for the
Check that there is not a short-
with power, even though outlets (on the back of the UPS) is open. circuit on the outlets.
button 16 is ON
Eliminate any overloads on the
(3200 RT only). outlets by modifying the
distribution of devices on the
outlets.
LED 26 flashes and UPS electronics have detected a UPS fault. Restart the UPS.
the buzzer sounds Depending on the UPS personalization parameters
continuously. (see section 3.4).
There are two possibilities:
The equipment connected to the UPS continues to Call the after-sales support
be supplied, but directly from the AC-power source department.
(via the automatic bypass (LED 19 ON).
The connected equipment is no longer supplied.
The equipment connected to the UPS is no
longer protected.
4. Maintenance