MGE UPS Systems 500 Rack Power Supply User Manual


 
34007117EN/AB - Page 29
6. Appendices
Technical characteristics
(1) The upper and lower thresholds may be set using the UPS Driver software.
(2) Or 40 Hz in low-sensitivity mode (may be set using the UPS Driver software).
(3) Adjustable from 200 to 240 V using the UPS Driver software.
Output rating
AC-input power
Voltage
Frequency
Output power (operation
on battery power)
Voltage
Frequency
Battery (sealed lead-acid,
maintenance free)
Tower models
Rack models
Environment
Noise level (operation on
AC-input power)
Operating temperature
Relative humidity
(without condensation)
Pulsar Evolution 500
500 VA / 350 W
2 x 6 V - 9 Ah,
1100 / 1100 rack
1100 VA / 700 W
2 x 12 V - 9 Ah,
4 x 6 V - 9 Ah
800 / 800 rack
800 VA / 560 W
2 x 12 V - 7.2 Ah,
4 x 6 V - 7.2 Ah
1500 / 1500 rack
1500 VA / 1000 W
3 x 12 V - 9 Ah,
6 x 6 V - 9 Ah
Single-phase, 160 V to 294 V
(1)
, 230V nominal.
Single-phase, 230 V
(3)
(+ 6% / - 10%)
50/60 Hz +/- 0.1 Hz
<40 dBA
0 to 35° C
20 to 90%
<40 dBA
0 to 40° C
20 to 90%
47 Hz to 70 Hz (50 Hz system) or 56.5 Hz to 70 Hz
(2)
(60 Hz system)