3.3 Logs
3.3.1 Measurements
Click on the “Measurements” section in the menu.
The following measurements are saved and time-stamped:
Z “Input voltage”: Value of the utility voltage supplying your UPS (average of 3 phases for UPS' equipped
with a 3-phase input)
Z “Input frequency”: Value of the utility frequency feeding your UPS
Z “Output voltage”: Value of the output voltage of your UPS (average of the 3 phases for UPS’ with a 3-
phase output)
Z “Output load”: Value of the percentage of load at UPS output (Value of the most loaded phase for 3-phase
UPS’)
Z “ Output current Ph x”: Value of the output current for each phase on three-phase UPSs
Z “Battery capacity”: Percentage of charge available in the battery
Z “Remaining time”: Estimation of the remaining backup time
Z The save frequency of these values is defined in the “System” page (60 seconds by default).
Approximately 1000 time-stamps are stored permanently on the card. The oldest time-stamps are
automatically deleted.
Z “Save” enables all saved values to be opened or saved in CSV format (compatible with Excel type
spreadsheets)
“Clear” enables deletion of all records. The administrator must enter his login / password to validate this
action if he has not already done so during the current session.
Select the time range to view