getting started
location
c observe the safety rules indicated at the
beginning of this document.
preliminary checks
c check that the "on/off" button " " on the
front is not pushed in;
c check that rating shown on the rating label
corresponds to the input voltage
specification and power requirement of the
load.
connections
c use the AC input cord to supply input
power to Pulsar as shown.
Connect the AC input cord between UPS
utility power input receptacle, and utility
power outlet.
c connect the computer loads to output
sockets 7 .
Note 1: following connection, the battery
automatically charges, whenever plugged in.
Note 2: the batteries will provide full back-up
time after approximatively 8 hours of
recharge time.
Note 3: the rating of input power cord must
be not less than the nominal input rating of
Pulsar EX: use the supplied cord.
Note 4: if site wiring fault LED 8 is lit and
buzzer sounds, line/neutral connections are
reversed.
c connection of the Pulsar EXB10/EXB15
battery extension module (optional):
v check that the button "on/off" " " on the
front of the Pulsar EX10/EX15 is not pushed
in,
v disconnect the input connection cord,
v flip the circuit-breaker of the battery unit to
the right (position "O"),
v connect the battery connection cord to the
DC connector of the battery module and
connect to the Pulsar EX10/EX15,
v if the installation has 2 battery modules,
connect the second cord to the DC
connector of the second module and to the
first module,
v the use of connectors is strictly limited to
connecting the battery modules to the
Pulsar EX10/EX15. Any other connection to
these connectors is prohibited and risks
damaging the battery, not covered by
warranty,
v to start, flip the battery circuit-breaker to
the left (position "I"),
v if your installation is operated with MGE
UPS SYSTEMS software, update your
battery configuration with EX Tuner.