MGE UPS Systems EX 5 RT 3:1 Power Supply User Manual


 
34007724EN/AA - Page 27
3. Operation
ON/OFF features
Factory setting
Disabled
Enabled
Enabled
Disabled
Enabled
Function
Cold start
Forced reboot
Automatic restart
Sleep mode
UPS ON/OFF by software
Options
Enabled
Disabled
Disabled
Enabled
Disabled
Comments
Start on battery.
Enables automatic restart of the system even
if normal AC source is restored before the end
of the shutdown sequence.
UPS restarts automatically
when normal AC source is restored.
Automatic shudown on battery if output load
level < 10%.
Enables consideration of shutdown or restart
orders from software to be authorized.
Battery features
Factory setting
Every week
20%
UPS reads # of battery
modules connected
Enabled
Function
Battery test
Low battery signal
Run time choice
Battery deep discharge
protection
Options
No test / daily / monthly
0 to 100%
From 50 to 400 Ah
Disabled
Comments
1% increment.
Requires Comet EX RT CLA if using options
(see section 1.4 "Battery extensions").
If disabled, lost of
MGE UPS SYSTEMS warranty.
Use EXIT key when set up is completed.
These parameters are only adjustable if UPS is OFF.
Access to the personalisation through external software
Insert the Solution-Pac CD ROM in your CD drive.
At the first Navigator Screen, select "Installation" and follow the instructions to install Personal Solution-Pac for
Windows.
If nothing appears, launch startup.exe
Then go to "Advanced settings" and "UPS settings".
Please note that the Linux/Unix/MacOS versions of Personal Solution-Pac do not include this feature.
3.2 Final start up sequence
Press the ON button more than 3 seconds.
After UPS internal test sequence, the green LED 13 goes on.
During the restart, if the Bypass AC source is out of tolerance, the UPS will generate an output 10 ms calibrated
break.