7. Before connecting the Battery Pack to an AC Source, verify that the Battery
Pack is set for the proper input voltage. Set the dipswitch on the rear panel
of the Battery Pack to the appropriate input voltage. Connect the input
power cord with the NEMA 5-15P Plug into the AC Inlet on the first Battery
Pack.
8. Connect the Daisy Chain power cord from the AC Outlet of the of the first
Battery Pack to the AC Inlet of the second Battery Pack.
9. Connect the input power cord (with the NEMA 5-15P Plug) from the first
Battery Pack into the AC wall outlet.
10. Turn ALL of the DC circuit breakers on the rear panel of the Battery Packs
to the On position.
11. The Battery Packs are ready for normal operation, see the UPS User's
Manual for the normal startup of the UPS.
NOTE: The maximum number that can be Daisy Chained for the AC source is
five Battery Packs. There is no maximum number for Daisy Chaining the DC
bus voltage for the Battery Packs.
NOTE: The EDBP72XL's External Battery Cable has a strain relief that
must be attached (with the screw) to the rear panel of the UPS and the
Daisy Chained Battery Packs.
EDBP72XL's External Battery Cable with strain relief.