Minuteman UPS MCP 10001 Power Supply User Manual


 
Page 5
Model Number
Battery Voltage
240 VDC
MCP6001
MCP10001
CAUTIONS:
The UPS contains voltages which are potentially hazardous. All repairs should be performed by qualified service person-
nel. The UPS has its own internal energy source (battery). The output may be ‘hot” even when the UPS is not connected to
the AC supply.
The voltage the internal batteries create is:
For the safety of the UPS, do not connect an imbalanced load.
An insulated grounding conductor should be identical in size, thickness, and insulation material to the grounded and
ungrounded branch-circuit supply conductors. The wire, which should be green or green with one or more yellow stripes,
is to be installed as part of the branch circuit that supplies the unit. Grounding conductor must be minimum #8 AWG wire.
The grounding conductor described in the above item shall be grounded to the earth end of the protected equipment.
These sealed non-spillable maintenance-free lead-acid batteries have pressure operated vents.
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required
precautions. Keep unauthorized personnel away from batteries.
When replacing batteries, replace with the same number of the following type: Matsushita (Panasonic) Electric Works
Type LCR12V7.2P (12V 7.2 AH), CSB Battery Co., Ltd Type GP1270F2 (12V 7.0AH) or Yuasa Type NP7-12 (12V7AH).
CAUTION - Do not dispose of any battery in a fire as it may explode. Lead-acid batteries generate hydrogen gas. Do
not smoke when near batteries.
CAUTION - Do not open or mutilate the battery or batteries. The electrolyte is a dilute sulfuric acid. Released electrolyte
is harmful to the skin and eyes. It may be toxic. It is electrically conductive and corrosive.
CAUTION - A battery can present a risk of electric shock and high short circuit current. The following precautions should
be observed when working on batteries:
Remove watches, rings and/or other metal objects.
Use tools with insulated handles.
Wear rubber gloves and boots. Wear full eye protection and protective clothing.
If electrolyte contacts the skin, wash it off immediately with water. If electrolyte contacts the eyes, flush thoroughly
and immediately with water. Seek medical attention.
Spilled electrolyte should be washed down with a suitable acid neutralizing agent. Use approximately 1pound of
bicarbonate soda to approximately one gallon of water. The solution should be added until reaction has ceased.
The resulting liquid should be flushed with water.
Do not lay tools or metal parts on top of batteries.
Discharge static electricity from body before touching batteries by first touching a grounded metal surface.
Disconnect charging source prior to connecting or disconnecting battery terminals.
Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of ground. Contact
with any part of a grounded battery can result in electric shock. The likelihood of such shock will be reduced if such
grounds are removed during installation and maintenance.
The safe and continuous operation of the UPS depends partially on the care taken by the user. Please note the following
precautions:
Do not disassemble the UPS.
Do not place the UPS near water or in an environment of excessive humidity.
Do not allow liquid or any foreign object to get inside the UPS.
Do not block air vents in the front of the UPS or air exhaust holes in the back.
Do not place the UPS under direct sunshine or close to heat-emitting source.
For prevention of UPS failure, please do not change the voltage setting switches while thew UPS is on.
HAZARDOUS VOLTAGE
Battery circuit is not isolated from the input voltage. There may be a hazardous voltage between battery terminals
and ground. Check it before touching!
Even after disconnection from the mains input voltage, components inside the UPS are still connected to the battery
and are )a hazardous potential. Disconnect the battery supply circuit before carrying out servicing or maintenance
work.