Minuteman UPS MCP 3000 Power Supply User Manual


 
0-138 (0-275 VAC)
88-138 (160-275 VAC)
>0.97
120VAC
(220/230/240 VAC)
0ms (true-on-line)
1000VA/700W
±2%
50 or 60Hz auto-sensing
Manual reset circuit breaker
50 or 60Hz ±2Hz
3%(Linear load); 6%(Rectifier load)
1 Hz/sec
105%-125% for 3 min., 125%-150% for 30 sec., > 150% for 1 sec.
3:1
80%
120 VAC (230 VAC) ±2%
50 or 60Hz ±1 Hz unless synchronized to utility during brownout
True sinewave
Over-current and short circuit protected, latching shutdown on overload
480J
6500 A maximum
0ns (instantaneous) normal mode, <5ns common mode
< 0.3% of peak, typical
(percentage of applied ANSI C62.41 cat A ±6V test wave form)
<5%
(As a percentage of an applied ±6kV 1.2/50ms, 500A 8/20ms test)
<1%
(As a percentage of an applied ±6kV 1.2/50ms, 500A 8/20ms test)
Normal and common mode EMI / RFI suppression
6ft. NEMA 5-15P
(IEC 320 C-14)
6 x NEMA 5-15R’s
4-Battery back-up
2-Surge protected only
(4 x IEC 320 C-13’s)
2-female DB-9’s(1-RS232 and 1-Dry Contact )
4 x 12V7AH
N/A
3 to 5 years depending on number of discharges and ambient temperature
2 to 4 hours from 50% discharge
0 to 40 degrees C (+32 to 104 degrees F)
-15 to +45 degrees C ( +5 to +113 degrees F)
0 to 95% non-condensing
0 to +3,000 m (0 to +10,000 ft.)
0 to +15,000 m (0 to +50,000 ft.)
IEC 801-2 LEVEL IV, 801-4 LEVEL IV, 801-5 LEVEL III
<45 dBA
32.2 x 18.8 x 40.5 cm
(12.7 x 7.4 x 15.9 in.)
20(24)Kg
44.1(52.9) lbs.
Listed to UL 1778 Compliance to CSA 22.2; (TUV/GS)
FCC Class A (2,3KVA) Class B (1KVA); (CE; TUV/EMC)
MCP 2000
(MCP 2000i)
*Options available. N/A for MCP 1000(i) All specifications subject to change without notice.
MCP 3000
(MCP 3000i)
120VAC
(208/220/230/240 VAC)
120VAC
(208/220/230/240 VAC)
2000VA/1400W
3000VA/2100W
83%
85%
6ft. NEMA 5-30P
(IEC 320 C-20)
6ft. NEMA 5-30P
(IEC 320 C-14)
4 x NEMA 5-15R’s and
1 x L5-30R
(6 x IEC 320 C-13’s)
4 x NEMA 5-15R’s and
1 x L5-30R
(6 x IEC 320 C-13’s)
6 x 12V7AH
8 x 12V7AH
OptionalOptional
32.2 x 18.8 x 47.6 cm
(12.7 x 7.4 x 18.7 in.)
32.2 x 18.8 x 55.5 cm
(12.7 x 7.4 x 21.9 in.)
28(32)Kg
61.7(70.6) lbs.
39.2(42.7)Kg
86.4(94.2) lbs.
NOTE: 230VAC Specs Shown In ( )
Acceptable Input Voltage
Input Voltage (on-line operation)
Power Factor
Output Voltage (on-line operation)
Transfer time
Maximum Load
Voltage regulation
Nominal input frequency
Input protection
Frequency limits (on-line operation)
THD
Slew Rate
Overload capacity
Crest factor
Efficiency
On-battery Output Voltage
On-battery frequency
On-battery wave shape
Protection
Surge energy rating
(one time 10/1000ms waveform)
Surge current capability (one time, 8/20ms
waveform)
Surge response time
Surge voltage let through
10 Base-T surge protection let-through
Telephone line surge protection let-through
Noise filter
Input(standard)*
Output receptacles(standard)*
Communication ports
Battery type: Spill proof, maintenance free,
sealed lead acid
Battery Pack
Typical battery life
Typical recharge time
Operating temperature
Storage temperature
Operating and storage relative humidity
Operating elevation
Storage elevation
Electromagnetic immunity
Audible noise at 1 m (3ft.)
Size (H x W x D)
Weight- Net (shipping)
Safety and approval
EMC Verification
18
MCP 1000
(MCP 1000i)