Minuteman UPS MN 525 Power Supply User Manual


 
10
DEFINITIONS FOR ILLUMINATED LED INDICATORS
Power
ON
Site
Wiring
Fault
Circuit
Breaker
Alarm
CONDITION
On Off Set Off
Normal Mode
Off On/Off Set
Two
Beeps
Utility Failure- the UPS is in the battery
mode.
Off On/Off Set
Rapid
Beeps
Utility Failure- The UPS is in the battery
mode and will run out of battery-power shortly.
Off Off Up
Two
Beeps
or
Rapid
Beeps
System Overload- Occurs when connected
equipment exceeds the rating of UPS. Turn
the UPS off, unplug at least one piece of
equipment, wait 10-seconds, reset the circuit
breaker and turn the UPS on.
Off On/Off Set
Long
Beep
Battery Overload- Occurs when connected
equipment exceeds the rating of battery-
powered outlets of the UPS. Turn the UPS off,
unplug at least one piece of equipment from
battery-powered outlets, wait 10-seconds,
reset the circuit breaker and turn the UPS on.
On/Off On Set None
Site Wiring Fault (MN 525 Only)- This indi-
cates a wiring problem with the AC wall outlet
such as bad ground, missing ground, or re-
versed wiring. Disconnect all electrical equip-
ment from the UPS’s outlets and have an
electrician check the AC wall outlet to ensure
proper wiring.