NPort 5600 Series User’s Manual Web Console Configuration
to 1200 bps, 8 data bits, 1 stop bit, and none for parity. In this case, the total number of bits needed
to send a character is 10 bits, and the time required to transfer one character is
( 10 (bits) / 1200 (bits/s) ) * 1000 (ms/s) = 8.3 ms.
Therefore, you should set Force transmit timeout to be larger than 8.3 ms, so in this case, it must
be greater than or equal to 10 ms.
If the user wants to send the series of characters in the same packet, the serial device attached to
NPort should send that series of characters during a time interval less than the Force Transmit
timeout for NPort, and the total length of data must be less than or equal to NPort’s internal buffer
size. The serial communication buffer size for NPort is 1 KB per port.
Destination IP address 1
Setting Factory Default Necessity
Begin: Empty
End: Empty
IP address range
E.g., Begin: 192.168.1.1
End: 192.168.1.10
Port: 4001
Required
Destination IP address 2/3/4
Setting Factory Default Necessity
Begin: Empty
End: Empty
IP address range
E.g., Begin: 192.168.1.11
End: 192.168.1.20
Port: 4001
Optional
Local listen port
Setting Factory Default Necessity
1 to 65535 4001 Required
The UDP port that NPort listens to, and that other devices must use to contact NPort. To avoid conflicts
with well known UDP ports, the default is set to 4001.
5-21