4-6
Network Settings
Setting Value Notes
Modbus Gateway Name Alphanumeric
Choose a name that easily
identifies the Gateway’s location,
function, etc.
IP Address
32-bit number,
default =
192.168.127.254
The IP (Internet Protocol)
address identifies the server on
the TCP/IP network.
Netmask
32-bit number,
default =
255.255.255.0
Identifies the server as belonging
to a Class A, B, or C network.
Default Gateway
32-bit number,
default =0.0.0.0
IP address of the router that
provides network access outside
the server’s LAN.
IP Configuration
Choose from Static
IP, DHCP, BootP, or
DHCP/BootP.
1. Choose Static IP if you are
using a fixed IP address.
2. Choose one of the other
options if the IP address is set
dynamically.
Modbus Settings
The Modbus Settings page is used to set up the Attached Serial Device type,
Initial delay time, and Modbus/TCP Slave device settings.
NOTE
To modify the settings on this page, first checkmark the Chan
g
e Modbus
Settings box.
The Modbus/TCP Slave device settings are only active if the attached
serial device is set as one of the two Master types.
Choose the Modbus protocol of the attached serial device to determine the
complementary Modbus protocol for the NPort 6110 Modbus Gateway. Four
different types of serial Modbus device can be used. Since the Modbus protocol
is used on a Master-Slave network, there are two steps to consider before starting
the configuration process. The first step is to determine which devices are
Masters and which are slaves (either Ethernet or Serial device). Next, you need
to determine the Modbus protocol that the serial device uses.