Safety Guidelines for Hazardous Locations
The cFP-PWM-520 is suitable for use in Class I, Division 2,
Groups A, B, C, D, T4 hazardous locations; Class I, Zone 2,
AEx nC IIC T4 and Ex nC IIC T4 hazardous locations; and
nonhazardous locations only. Follow these guidelines if you are
installing the cFP-PWM-520 in a potentially explosive
environment. Failing to follow these guidelines may result in
serious injury or death.
Caution Make sure that all products you use in hazardous
locations are certified for such use. Refer to the product
label or visit
ni.com/certification, search by model
number or product line, and click the appropriate link in
the Certification column.
Caution Do not disconnect I/O-side wires or connectors
unless power has been switched off or the area is known
to be nonhazardous.
Caution Do not remove modules unless power has been
switched off or the area is known to be nonhazardous.
Caution Substitution of components may impair
suitability for Class I, Division 2.
Caution For Zone 2 applications, install the Compact
FieldPoint system in an enclosure rated to at least IP 54
as defined by IEC 60529 and EN 60529.
Caution For Zone 2 applications, install a protection
device across the external power supply and the COM
terminal. The device must prevent the external power
supply voltage from exceeding 42 V if there is a transient
overvoltage condition.
Special Conditions for Hazardous Locations Use in Europe
The cFP-PWM-520 has been evaluated as EEx nC IIC T4
equipment under DEMKO Certificate No. 03 ATEX 0251502X.
Each module is marked II 3G and is suitable for use in Zone 2
hazardous locations.