Overload protection ..........................Protected against short
circuits and output overload
Physical
Indicator............................................Green DC POWER LED
Weight............................................... 300 g (10.5 oz)
Environmental
FieldPoint modules are intended for indoor use only.
Operating temperature
15 W operation...........................0 to 50 °C
10 W operation...........................50 to 60 °C
Storage temperature..........................40 to +85 °C
Humidity...........................................10 to 90% RH,
noncondensing
Maximum altitude.............................2,000 m
Pollution degree................................2
Safety
Do not operate FieldPoint products in an explosive atmosphere or
where there may be flammable gases or fumes. If you need to
operate FieldPoint products in such an environment, the FieldPoint
products must be in a suitably rated enclosure. The FP-PS-4 meets
the requirements of the following standards for safety and
electrical equipment for measurement, control, and laboratory use:
EN 61010-1:1993/A2:1995, IEC 61010-1:1990/A2:1995
UL 3121-1:1998
CAN/CSA C22.2 no. 1010.1:1992/A2:1997
Electromagnetic Compatibility
CE, C-Tick and FCC Part 15 (Class A) Compliant
Electrical emissions ..........................EN 55011 Class A at 10 m
FCC Part 15A above 1 GHz
Electrical immunity ..........................Evaluated to EN 61326:
1997/A1: 1998, Table 1
Note
For full EMC compliance, you must operate this
device with shielded cabling. See the Declaration of
Conformity (DoC) for this product for any additional