Panduit PN380 Network Card User Manual


 
PANDUIT DPoE Power System User’s Guide Issue 1.0
Part Number: PN380
CAUTION:
ALWAYS FOLLOW NEC GUIDELINES AND YOUR LOCAL COMPANY
PRACTICES WHEN SELECTING DC WIRING AND PROTECTION.
Table 5: Minimum Recommended DC AWG for 90° C Cabling for Unprotected Outputs shows
recommended wire sizes based on ampacity. The maximum current rating for the chassis is 100 A.
Rectifiers
Single hole bulk
battery connections
(¼" studs)
14 GMT Fuse
Connections
141 2
Figure 2: DC Wire Diagram
Each chassis is equipped with 14 GMT style fuse connections and an unfused bulk DC connection
located on the rear of the chassis. The GMT fused connections are made on “lugless” terminal blocks
with compression screws.
The bulk DC connection may be used as a battery input or as an unfused bulk output. The connections
require a terminal lug (1/4” single hole lug with a max tongue width of 0.63” or less). Size wires based on
the total rectifier capacity and choose conductor size according to Table 5: Minimum Recommended DC
AWG for 90° C Cabling for Unprotected Outputs .
Connecting to a DPoE Power Patch Panel
Each DPoE Power Patch Panel is shipped with a keyed power connector harness and two butt splices
(PANDUIT part number BSV14X) for use in connecting the panel to the power source. The butt splices
included with the DPoE Power Patch Panel will support 14 - 16 AWG solid or stranded wire.
WARNING:
Connect each DPoE Power Patch Panel to the rear of the DPoE Power
System using one of the 14 GMT-fused outputs per panel.
DO NOT WIRE MULTIPLE PANELS TO A SINGLE OUTPUT ON THE
DPoE POWER SYSTEM.
5