PANDUIT DPoE Power System User’s Guide Issue 1.0
Part Number: PN380
Table 5: Minimum Recommended DC AWG for 90° C Cabling for
Unprotected Outputs
Total Rectifier Current
Rating (A)
Wire and Lug Gauge
(AWG) using 90° C wire
(NEC Table 310.16)
1
10 16
20 14
25 12
30 12
40 10
50 8
75 6
Torque Settings
The following table shows recommended torque settings for all mechanical and electrical connections
according to screw or nut size in inch pounds (in-lbs).
Table 6: Recommended Torque Settings
Screw or Nut Size Toque (in-lbs)
4-40 6
6-32 12
8-32 22
10-32 37
12-24 50
¼-20 65
Required Tools
The DPoE Power System is designed to be installed with a minimum number of commonly available
tools:
• #1 & #2 flat blade and Phillips head screwdrivers
• Torque wrench
• 7/16” socket, ¼” drive
• Wire and cable strippers (PANDUIT part number CT-100)
• Wire and cable crimpers (such as PANDUIT part CT-1550, CT-1551, CT-1570, CT-1700
Contour Crimp
TM
Controlled Cycle Crimp Tools) (used for optional bulk DC connection)
Site and Equipment Preparation
Prior to unpacking the DPoE Power System, note any physical package damage that could indicate
potential damage to the contents. After removing DPoE Power System from the boxes and packing
material, inspect for shipping and/or other damage. Any problems should be reported to PANDUIT
technical support.
7
1
Table 310.16 uses Table 3B – Sizes of Conductors from BS EN 60950:2000, “Safety of Information
Technology Equipment,” December 2000 for non-building wiring.