PD-6006/12/24
Power over LAN Solutions 6 Cat. No.: 06-6800-056
1.2 Power Cord
In the event that the power cord is replaced, the replacement must meet local
requirements.
U.S.A. and
Canada
The cord must be UL-approved or CSA certified.
The minimum specification for the flexible cord is:
• No. 18 AWG
• Type SV or SJ
• Three-conductor.
The cord set must have a rated current capacity of at least
10 A.
The attachment plug must be an earth-grounding type with a
NEMA 5-15P (15 A, 125 V) or NEMA 6-15P (15 A, 250 V)
configuration.
Denmark
The supply plug must comply with section 107-2-D1,
standard DK2-1a or DK2-5a.
Switzerland
The supply plug must comply with SEV/ASE 1011.
The appliance coupler (connecting to the Midspan and not to
the wall plug) must have a configuration for mating with an
EN60320/IEC320 appliance inlet.
The power socket outlet must be near the Midspan and be
easily accessible. You can only remove power from the unit by
disconnecting the power cord from the outlet.
This unit operates under SELV (Safety Extra Low Voltage)
conditions according to EN60950/IEC 950. The conditions are
only maintained if the equipment to which it is connected also
operates under SELV conditions.
France and Peru only: This unit cannot be powered from IT
supplies. If your supplies are of IT type, this unit must be
powered by 230 V (2P+T), via an isolation transformer with a
ratio of 1:1 and with the secondary connection point labeled
Neutral, connected directly to ground.
U.K. only: The Power over LAN Midspan is covered by
General Approval, NS/G/12345/J/100003, for indirect
connection to a public telecommunications system.