POWERWARE 9125 BATTERY BACKUP TIMES (in minutes)
700-1000 VA Models
Load Standard
(VA/Watts) Internal Batteries +1 EBM +2 EBMs
200/140 37 271 546
400/280 19 142 278
700/490 9 72 156
850/595 6 59 124
1000/700 5 48 104
1250-2000 VA Models
Load Standard
(VA/Watts) Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
400/280 46 177 331 501 682
700/490 25 96 180 272 370
850/595 21 76 142 214 292
1000/700 16 61 115 174 237
1250/875 11 46 87 131 179
1500/1050 8 37 70 106 144
1800/1260 6 30 57 85 116
2000/1400 5 26 49 74 100
2500-3000 VA Models
Load Standard
(VA/Watts) Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
1250/875 16 57 90 150 200
1500/1050 13 55 72 120 160
2500/1750 7 28 48 68 88
3000/2100 5 25 38 54 70
Note: Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
POWERWARE 9125 EBC BACKUP TIMES (in minutes)
1
Discharge Time
EXTERNAL EBC-48 CABINETS. For use with 1250, 1500, 2000 VA
VA Watts +1 EBC-48 +2 EBC-48s +3 EBC-48s
650 455 838
800 560 662
1000 700 506
1200 840 406
1250 875 387
1400 980 340 761
1500 1050 315 705
1600 1120 294 658
1800 1260 258 578
2000 1400 224 501 802
EXTERNAL EBC-72 CABINETS. For use with 2500, 3000 VA
VA Watts +1 EBC-72 +2 EBC-72s +3 EBC-72s +4 EBC-72s
1000 700 387
1500 1050 245
2000 1400 175 368
2500 1750 135 284 446
3000 2100 107 225 354 490
1. Actual runtimes not supported by Powerware LanSafe software. *Discharge time @100% of the UPS rating.
Note: Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
SINGLE-PHASE SERIES 9
Powerware 9125 (700–3000 VA) EBM Backup Times