Powerware 15 KVA Power Supply User Manual


 
OPERATION
EATON Powerware
®
9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com
75
UPS Shutdown
To shut down the UPS:
1. Press any button on the front panel display to activate the menu
options.
2. Press the
button on the front panel display and then press the
button to select the TURN UPS ON/OFF menu.
3. Select the OFF option; press the
button.
4. Confirm the selection; press the
button.
5. Press and hold the
button for three seconds, until the UPS stops
beeping.
The input contactor opens.
6. Switch the UPS battery circuit breaker to the OFF position.
The UPS is disconnected from the batteries and is on logic power
only.
7. Switch off utility power where the UPS is connected.