Chapter 6 Specifications
Table 12. Dimensions and Weight
Component Weight Dimensions (WxHxD)
Electronics module
(dual panel with display)
8.2 kg (18 lb)
377 284 118 mm
(14.8"
11.2" 4.6")
Electronics module
(dual panel without display)
7.7 kg (17 lb)
377 284 113 mm
(14.8"
11.2" 4.5")
Conduit box (each side) 1.6 kg (3.6 lb)
128 287 113 mm
(5.0"
11.3" 4.5")
Mounting bracket 1.5 kg (3.4 lb) See Note 2
Harnesses (each):
Branch circuit
Voltage
Main input
0.7 kg (1.6 lb)
0.4 kg (0.8 lb)
0.2 kg (0.4 lb)
Ċ
Split−core CTs (each):
Branch, 75A
Branch, 100A
Main, 400A
Input ground, 100A
0.07 kg (0.15 lb)
0.10 kg (0.22 lb)
0.71 kg (1.56 lb)
0.51 kg (1.13 lb)
Ċ
Advanced Metering external cables 0.9 kg (2 lb) Ċ
NOTE 1 Weight varies depending on installed options.
NOTE 2 Weights and dimensions for electronics module include mounting bracket but do not include connectors or
reset switch. Dimensions vary depending on installed options.
Table 13. Communication Options
X−Slot Communication Bay Power Xpert Gateway Series 1000 Card
Serial Port DB−9 (RS−232)
Signal Inputs (4) programmable inputs (signal and signal return)
for indicating building alarms or other use
NOTE Signal only (at 17 mA); action power must be supplied externally.
Relay Output Contacts (1) relay output for indicating alarm condition present
NO and NC relay contacts are rated at 8A at 32 Vdc or less, derate to 1A at 60 Vdc.