43
Powerware
®
5115 Rack-Mount User’s Guide : 164201449 RevA www.powerware.com
CHAPTER 8
SPECIFICATIONS
This section provides the following specifications for the
Powerware 5115 RM models:
: Dimensions and weights
: Electrical input and output
: Environmental and safety
: Battery
Table 3. Model List and Mechanical
120V Models 230V Models
UPS Models PW5115 500 RM
PW5115 750 RM
PW5115 1000 RM
PW5115 1500 RM
PW5115 500iRM
PW5115 750iRM
PW5115 1000iRM
PW5115 1500iRM
UPS Dimensions (WxHxD) 44.0 x 4.45 x 57.8 cm (17.3 x1.75 x 22.75)
UPS Weights 500 VA: 17.36 kg (38.2 lb)
750–1000 VA: 20.23 kg (44.5 lb)
1500 VA: 22.95 kg (50.5 lb)
Table 4. Electrical Input
120V Models 230V Models
Nominal Voltage 120V default; 110V, 120V selectable 230V default; 220V, 230V, 240V selectable
Voltage Range ±20% for nominal voltage at full load
Nominal Frequency 45–65 Hz, 50/60 Hz auto-sensing
Efficiency (Normal mode) 95%
Noise Filtering Full-time EMI/RFI filtering
Overcurrent Protection AC source overcurrent protection device Resettable input circuit protector
Connections 6-ft, 5-15P power cord 10A, IEC-320 input connector