Table 8. Troubleshooting Guide (continued)
Alarm or Condition Possible Cause Action
1 beep The UPS is running on Correct the input voltage, if possible. The UPS
every 2 battery power because the continues to operate on battery until the condition is
seconds input voltage is too high or corrected or the battery is completely discharged.
too low. If the condition persists, the input voltage in your area
may differ from the UPS nominal.
1 beep per Power requirements exceed The UPS will automatically shut down in 3 minutes.
second UPS capacity (overload is Save your work immediately and turn off your
greater than 120%) or the equipment. Turn off the UPS.
load is defective. Remove some of the equipment from your UPS. You.
may need to obtain a larger capacity UPS.
1 beep per The UPS is on battery and Shutdown is imminent (30 seconds). Save your work
second the power requirements and turn off your equipment. Turn off the UPS.
exceed UPS capacity Remove some of the equipment from the UPS. You
(overload is greater than may need to obtain a larger capacity UPS.
120%) or the load is
defective.
Continuous Battery test failed. Check the battery connections and be sure the
beep battery is fully charged.
If the indicator still flashes, see “UPS
Maintenance” on page 15 to replace the battery. Call
your service representative if the problem persists
Continuous UPS internal temperature is Shutdown is imminent. Save your work and turn off
beep too high. your equipment. Turn off the UPS.
Clear vents and remove any heat sources. Wait at
least 5 minutes and restart the UPS. If the condition
persists, contact your service representative.
Continuous UPS fan fault (750-1400VA Save your work and turn off your equipment. Turn off
beep models only) the UPS. Contact your service representative.