Powerware 700 VA Network Card User Manual


 
13
Powerware
®
3110 User’s Guide S Rev B www.powerware.com
CHAPTER 4
SPECIFICATIONS
Powerware Corporation reserves the right to change specifications
without prior notice.
Table 2. Electrical
120V Model 230V Model
Nominal Voltage 120V 230V
Power Factor 0.6
Voltage Range Online: 90–152V
On Battery: 0–100V and 152–160V
Online: 176–272V
On Battery: 0–192V and 272–290V
Nominal Frequency 50/60 Hz auto-sensing
57–63 Hz (60 Hz)
47–53 Hz (50 Hz)
Efficiency
(Normal mode)
> 95%
Noise Filtering Full-time EMI/RFI filtering
Overcurrent Protection Resettable circuit breaker
Connections Attached 5-15P power cord IEC 320-C14 input connector
Input fault current: 15A maximum
Power Levels
(rated at nominal
inputs)
PW3110 300: 300 VA, 180W
PW3110 550: 550 VA, 330W
PW3110 700: 700 VA, 420W
PW3110 300i: 300 VA, 180W
PW3110 550i: 550 VA, 330W
PW3110 700i: 700 VA, 420W
Total Output Current 10A maximum
Load Compatibility Switch-mode power supply or resistive load
Output Frequency
(Battery mode)
50/60 Hz ±1 Hz of nominal frequency
Connections (4) 5-15 receptacles with UPS
and surge protection
(2) 5-15 receptacles with surge
protection only
(4) IEC 320-C13 receptacles with UPS
and surge protection
(2) IEC 320-C13 receptacles with surge
protection only